BENSHAW ENHANCED KEYPAD User Manual Page 114

  • Download
  • Add to my manuals
  • Print
  • Page
    / 182
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 113
106
Vmet Span I/O 34
Imet Span I/O 35
I/O: Vmet Span
34 100.0%
I/O: Imet Span
35 100.0%
7 - PARAMETER DESCRIPTION
LCD Display
Range 0.0 to 200.0% (Default 100.0%)
Description This parameter is used to alter the range of the output at the Vmet analog output terminals. For
example, for Vmet, setting this parameter to a value of 50% alters the range to 0 to 5VDC.
See also I/O 32
LCD Display
Range 0.0 to 200.0% (Default 100.0%)
Description This parameter is used to alter the range of the output at the Imet analog output terminals. For example,
with a 4-20mA output, a value of 50%will alter the range to 4-12mA output.
See also I/O 33, 36
ImetOffset I/O36
I/O: Imet Oset
36 0.0%
LCD Display
Range 0.0% to 100.0% (Default 0.0%)
Description This parameter adjust the low-end offset for the current analog output Imet. For example, if the value of
this parameter was set to 50%, the range for the output would start at 10mA rather than 4mA.
See also I/O 32, 35